• H1Z2Z2-K
AC:1.0/1.0 kV XL -HFFR INSULATED SINGLE CORE SOLAR CABLE

AC: 1.0/1.0 kV XL -HFFR INSULATED SINGLE CORE SOLAR CABLE
| Code | H1Z2Z2-K |
| Standarts | EN 50618 |
| Construction | Electrolytic tinned copper, fine stranded class 5 conductor, XL-HFFR cross-linked insulation, XL-HFFR cross-linked outer sheath. |
| Application | Used in solar power systems for connections between solar panels and system components such as inverters. Suitable for installation in cable ducts and cable trays, in indoor and outdoor applications. |
| Technical Datas | Operating temperature is between -40°C and +90°C
Minimum installation temperature is -25°C Minimum bending radius is 4*D D: Cable’s outer diameter(mm) |
- Product Description
|
Dimensions & Weights
|
Electrical Data | |||||
|
Nominal
cross section
|
Overall
Diameter
|
Net Weight
|
Maximum
permissible
tensile force
|
Conductor DC resistance at 20 °C (Maximum) |
Current carrying capacity at 60°C ambient temperature |
|
|
On surface (A)
|
In free air (A)
|
|||||
| mm² | mm |
kg/km
|
Max. (N)
|
ohm/km
|
||
| 1.5 | 4.6 | 35 | 23 | 13,7 | 29 | 30 |
| 2.5 | 5.0 | 45 | 38 | 8,21 | 39 | 41 |
| 4 | 5.6 | 60 | 60 | 5,09 | 52 | 55 |
| 6 | 6.1 | 80 | 90 | 3,39 | 67 | 70 |
| 10 | 7.2 | 124 | 150 | 1,95 | 93 | 98 |
| 16 | 9.2 | 195 | 240 | 1,24 | 125 | 132 |
| 25 | 10.8 | 286 | 375 | 0,795 | 167 | 176 |
| 35 | 12.4 | 395 | 525 | 0,565 | 207 | 218 |
| 50 | 14.6 | 545 | 750 | 0,393 | 262 | 276 |
| 70 | 17.2 | 745 | 1050 | 0,277 | 330 | 347 |
| 95 | 19.4 | 975 | 1425 | 0,210 | 395 | 416 |
| 120 | 21.5 | 1230 | 1800 | 0,164 | 464 | 488 |
| 150 | 24 | 1558 | 2250 | 0,132 | 538 | 566 |
| 185 | 27.4 | 1927 | 2775 | 0,108 | 612 | 644 |
| 240 | 30.3 | 2443 | 3600 | 0,0817 | 736 | 775 |